B−41
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1415h
Output [11]
function
C021 R/W
0 (RUN: running), 1 (FA1: constant-speed reached), 2
(FA2: set frequency overreached), 3 (OL: overload
notice advance signal (1)), 4 (OD: output deviation for
PID control), 5 (AL: alarm signal), 6 (FA3: set
frequency reached), 7 (OTQ: over-torque), 9 (UV:
undervoltage), 10 (TRQ: torque limited), 11 (RNT:
operation time over), 12 (ONT: plug-in time over), 13
(THM: thermal alarm signal), 19 (BRK: brake release),
20 (BER: braking error), 21 (ZS: 0 Hz detection
signal), 22 (DSE: speed deviation maximum), 23
(POK: positioning completed), 24 (FA4: set frequency
overreached 2), 25 (FA5: set frequency reached 2), 26
(OL2: overload notice advance signal (2)), 31 (FBV:
PID feedback comparison), 32 (NDc: communication
line disconnection), 33 (LOG1: logical operation result
1), 34 (LOG2: logical operation result 2), 35 (LOG3:
logical operation result 3), 39 (WAC: capacitor life
warning), 40 (WAF: cooling-fan), 41 (FR: starting
contact signal), 42 (OHF: heat sink overheat warning),
43 (LOC: low-current indication signal), 44 (M01:
general-purpose output 1), 45 (M02: general-purpose
output 2), 46 (M03: general-purpose output 3), 50
(IRDY: inverter ready), 51 (FWR: forward rotation), 52
(RVR: reverse rotation), 53 (MJA: major failur)
54 (WCO: window comparator O), 55 (WCO: window
comparator OI),
58(FREF),59(REF),60(SETM),62(EDM),63(OPO:Opti
on)
-
1416h
Output [12]
function
C022 R/W -
1421h to
1423h
(Reserved) - - -
141Ah
Alarm relay
function
C026 R/W -
141Bh
[EO] terminal
selection
C027 R/W
0 (output frequency), 1 (output current), 2 (output
torque), 3 (digital output frequency), 4 (output
voltage), 5 (input power), 6 (electronic thermal
overload), 7 (LAD frequency), 8 (digital current
monitoring), 10 (heat sink temperature), 12
(general-purpose output YA0),15 ,16(option)
-
141Ch
[AM] terminal
selection
C028 R/W
0 (output frequency), 1 (output current), 2 (output
torque), 4 (output voltage), 5 (input power), 6
(electronic thermal overload), 7 (LAD frequency), 10
(heat sink temperature), 11 (output torque [signed
value]), 13 (general-purpose output YA1),16(option)
-
141Dh (reserved) - - - -
141Eh
Digital current
monitor reference
value
C030 R/W 200 to 2000 0.1 [%]
141Fh
Output [11] active
state
C031 R/W 0 (NO), 1 (NC) -
1420h
Output [12] active
state
C032 R/W 0 (NO), 1 (NC) -
1421h to
1423h
(Reserved) - - - -
1424h
Alarm relay active
state
C036 R/W 0 (NO), 1 (NC) -
1425h (Reserved) - - - -
1426h
Output mode of
low current
detection
C038 R/W
0 (output during acceleration/deceleration and
constant-speed operation), 1 (output only during
constant-speed operation)
-
1427h
Low current
detection level
C039 R/W 0 to 2000 0.1 [%]
1428h
Overload signal
output mode
C040 R/W
00 (output during acceleration/deceleration and
constant-speed operation), 01 (output only during
constant-speed operation)
-
1429h
Overload warning
level
C041 R/W 0 to 2000 0.1 [%]