B40
Parameter group C
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1401h Input [1] function C001 R/W
1 (RV: Reverse RUN), 2 (CF1: Multispeed 1 setting),
3 (CF2: Multispeed 2 setting), 4 (CF3: Multispeed 3
setting), 5 (CF4: Multispeed 4 setting), 6 (JG:
Jogging), 7 (DB: external DC braking), 8 (SET: Set
2nd motor data), 9 (2CH: 2-stage
acceleration/deceleration), 11 (FRS: free-run stop), 12
(EXT: external trip), 13 (USP: unattended start
protection), 14: (CS: commercial power source
enable), 15 (SFT: software lock), 16 (AT: analog input
voltage/current select), 18 (RS: reset), 20 (STA:
starting by 3-wire input), 21 (STP: stopping by 3-wire
input), 22 (F/R: forward/reverse switching by 3-wire
input), 23 (PID: PID disable), 24 (PIDC: PID reset, 27
(UP: remote control UP function), 28 (DWN: remote
control DOWN function), 29 (UDC: remote control
data clearing), 31 (OPE: forcible operation), 32 (SF1:
multispeed bit 1), 33 (SF2: multispeed bit 2), 34 (SF3:
multispeed bit 3), 35 (SF4: multispeed bit 4), 36 (SF5:
multispeed bit 5), 37 (SF6: multispeed bit 6), 38 (SF7:
multispeed bit 7), 39 (OLR: overload restriction
selection), 40 (TL: torque limit enable), 41 (TRQ1:
torque limit selection bit 1), 42 (TRQ2: torque limit
selection bit 2), 44 (BOK: braking confirmation), 46
(LAC: LAD cancellation), 47 (PCLR: clearance of
position deviation), 50 (ADD: trigger for frequency
addition [A145]), 51 (F-TM: forcible-terminal
operation), 52 (ATR: permission of torque command
input), 53 (KHC: cumulative power clearance), 56
(MI1: general-purpose input 1), 57 (MI2:
general-purpose input 2), 58 (MI3: general-purpose
input 3), 59 (MI4: general-purpose input 4), 60 (MI5:
general-purpose input 5), 61 (MI6: general-purpose
input 6), 62 (MI7: general-purpose input 7), 65 (AHD:
analog command holding), 66 (CP1: multistage
position settings selection 1 ), 67 (CP2: multistage
position settings selection 2), 68 (CP3: multistage
position settings selection 3), 69 (ORL: Zero-return
limit function), 70 (ORG: Zero-return trigger function),
73 (SPD: speed / position switching), 77 (GS1: safety
input 1), 78 (GS2: safety input 2), 81 (485: EzCOM),
82 (PRG: executing EzSQ program), 83 (HLD: retain
output frequency), 84 (ROK: permission of run
command), 85 (EB: Rotation direction detection(for V/f
with ENC), 86 (DISP: Display limitation),
255 (no: no assignment),
-
1402h Input [2] function C002 R/W -
1403h Input [3] function C003 R/W -
1404h Input [4] function C004 R/W -
1405h Input [5] function C005 R/W -
1406h Input [6] function C006 R/W -
1407h Input [7] function C007 R/W -
1408h to
140Ah
(Reserved) - - Inaccessible -
140Bh
Input [1] active
state
C011 R/W 0 (NO), 1 (NC) -
140Ch
Input [2] active
state
C012 R/W 0 (NO), 1 (NC) -
140Dh
Input [3] active
state
C013 R/W 0 (NO), 1 (NC) -
140Eh
Input [4] active
state
C014 R/W 0 (NO), 1 (NC) -
140Fh
Input [5] active
state
C015 R/W 0 (NO), 1 (NC) -
1410h
Input [6] active
state
C016 R/W 0 (NO), 1 (NC) -
1411h
Input [7] active
state
C017 R/W 0 (NO), 1 (NC) -
1412h to
1414h
(Reserved) - - Inaccessible -