B39
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1375h to
137Ah
(Reserved) - - - -
137Bh Brake Control Enable b120 R/W 0 (disabling), 1 (enabling) -
137Ch Brake Wait Time for Release b121 R/W 0 to 500
0.01
[sec.]
137Dh Brake Wait Time for Acceleration b122 R/W 0 to 500
0.01
[sec.]
137Eh Brake Wait Time for Stopping b123 R/W 0 to 500
0.01
[sec.]
137Fh Brake Wait Time for Confirmation b124 R/W 0 to 500
0.01
[sec.]
1380h Brake Release Frequency b125 R/W 0 to 40000 0.01 [Hz]
1381h Brake Release Current b126 R/W 0 to 2000 0.1 [%]
1382h Braking frequency b127 R/W 0 to 40000 0.01 [Hz]
1383h (Reserved) - - - -
1384h (Reserved) - - - -
1385h
Deceleration overvoltage
suppression enable
b130 R/W
0 (disabling), 1 (enabling), 2 (enabling with
acceleration)
-
1386h Decel. overvolt. suppress level b131 R/W
200 V class: 330 to 390 (V)
400 V class: 660 to 780 (V)
1 [V]
1387h Decel. overvolt. suppress const. b132 R/W 10 to 3000
0.01
[sec.]
1388h
Decel. overvolt. suppress
propotional gain
b133 R/W 0 to 500 0.01
1389h
Decel. overvolt. suppress Integral
time
b134 R/W 0 to 1500 0.1 [sec.]
138Ah to
1393h
(Reserved) - - - -
1394h
GS input mode
b145 R/W 0(non Trip) /1(Trip)
1395h
1399h
(Reserved) - - -
139Ah Display ex.operator connected b150 R/W 001 to 060
139Bh
13A2h
(Reserved) - - -
13A3h
1st parameter of Dual
Monitor
b160 R/W 001 to 030
13A4h
2nd parameter of Dual
Monitor
b161 R/W 001 to 030
13A5h
(Reserved) - - -
13A6h
Freq. set in monitoring
b163 R/W 0 (disabling), 1 (enabling),
13A7h
Automatic return to the initial
display
b164 R/W 0 (disabling), 1 (enabling),
13A8h Ex. operator com. loss action b165 R/W
0 (tripping), 1 (tripping after decelerating and
stopping the motor), 2 (ignoring errors),
3 (stopping the motor after free-running),
4 (decelerating and stopping the motor)
13A9h
13ADh
(Reserved) - - -
13AEh
Inverter mode selection
b171 R/W
0 (disabling), 1 (IM mode), 2 (High Freq.
mode)
13AFh
13B6h
(Reserved) - - -
13B7h
Initialization trigger
b180 R/W 0 (disabling), 1 (enabling),
13B8h
1400h
unused - - Inaccessible -