B38
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1345h to
1348h
(Reserved) - - -
1349h Operation level at O disconnection b070 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Ah Operation level at OI disconnection b071 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Bh to
134Dh
(reserved) - - - -
134Eh Ambient temperature b075 R/W -10 to 50
1 []
134Fh to
1350
(reserved) - - - -
1351h
Cumulative input power data
clearance
b078 R/W Clearance by setting "1" -
1352h Watt-hou
r
display gain b079 R/W 1 to 1000 1
1353h to
1354h
(Reserved) - - - -
1355h Start frequency b082 R/W 10 to 999 0.01 [Hz]
1356h Carrier frequency b083 R/W 20 to 150 0.1 [kHz]
1357h
Initialization mode (parameters or
trip history)
b084 R/W
0,1 (clearing the trip history), 2 (initializing
the data), 3 (clearing the trip history and
initializing the data), 4 (clearing the trip
history and initializing the data and EzSQ
program)
-
1358h Country code for initialization b085 R/W 0 (area A), 1 (area B) -
1359h
Frequency scaling conversion
facto
r
b086 R/W 1 to 9999 0.01
135Ah STOP key enable b087 R/W
0 (enabling), 1 (disabling), 2 (disabling only
stop)
-
135Bh Restart mode after FRS b088 R/W
0 (starting with 0 Hz), 1 (starting with
matching frequency), 2 (starting with active
matching frequency)
-
135Ch
Automatic carrier frequency
reduction
b089 R/W
0(disabling)/1(enabling( output current
controlled))/
2(enabling( fin temperature controlled))
-
135Dh Dynamic braking usage ratio b090 R/W 0 to 1000 0.1 [%]
135Eh Stop mode selection b091 R/W 0 (deceleration until stop), 1 (free-run stop) -
135Fh Cooling fan control b092 R/W
0 (always operating the fan), 1 (operating the
fan only during inverter operation [including 5
minutes after powe
r
-on and powe
r
-off]) ,2
-
1360h Clear elapsed time of cooling fan b093 R/W 0(count)/1(clear)
-
1361h Initialization target data b094 R/W 0 to 3
-
1362h Dynamic braking control b095 R/W
0 (disabling), 1 (enabling [disabling while the
motor is stopped]), 2 (enabling [enabling also
while the motor is stopped])
1363h Dynamic braking activation level b096 R/W 330 to 380, 660 to 760 1. [V]
1364h to
1366h
(Reserved) - - - -
1367h Free-setting V/f frequenc
y
(1) b100 R/W 0. to "free-setting V/f frequency (2)" 1 [Hz]
1368h Free-setting V/f voltage (1) b101 R/W 0. to 8000 0.1 [V]
1369h Free-setting V/f frequency (2) b102 R/W 0. to "free-setting V/f frequency (3)" 1 [Hz]
136Ah Free-setting V/f voltage (2) b103 R/W 0. to 8000 0.1 [V]
136Bh Free-setting V/f frequency (3) b104 R/W 0. to "free-setting V/f frequency (4)" 1 [Hz]
136Ch Free-setting V/f voltage (3) b105 R/W 0. to 8000 0.1 [V]
136Dh Free-setting V/f frequency (4) b106 R/W 0. to "free-setting V/f frequency (5)" 1 [Hz]
136Eh Free-setting V/f voltage (4) b107 R/W 0. to 8000 0.1 [V]
136Fh Free-setting V/f frequency (5) b108 R/W 0. to "free-setting V/f frequency (6)" 1 [Hz]
1370h Free-setting V/f voltage (5) b109 R/W 0. to 8000 0.1 [V]
1371h Free-setting V/f frequency (6) b110 R/W 0. to "free-setting V/f frequency (7)" 1 [Hz]
1372h Free-setting V/f voltage (6) b111 R/W 0. to 8000 0.1 [V]
1373h Free-setting V/f frequency (7) b112 R/W 0. to 400. 1 [Hz]
1374h Free-setting V/f voltage (7) b113 R/W 0. to 8000 0.1 [V]