C8
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
a084
AVR deceleration gain Gain adjustment of the braking
performance, range is 50 to
200%
U
100. %
A085
Energy-saving operation
mode
Two option codes:
00Normal operation
01Energy-saving operation
U
00
A086
Energy-saving mode tuning Range is 0.0 to 100 %.
U
50.0 %
A092
Acceleration time (2) Duration of 2
nd
segment of
acceleration, range is:
0.01 to 3600 sec.
9
10.00 sec
A292
Acceleration time (2),
2
nd
motor
9
10.00 sec
A093
Deceleration time (2) Duration of 2
nd
segment of
deceleration, range is:
0.01 to 3600 sec.
9
10.00 sec
A293
Deceleration time (2),
2
nd
motor
9
10.00 sec
A094
Select method to switch to
Acc2/Dec2 profile
Three options for switching
from 1st to 2nd accel/decel:
002CH input from terminal
01Transition frequency
02Forward and reverse
U
00
A294
Select method to switch to
Acc2/Dec2 profile, 2
nd
motor
U
00
A095
Acc1 to Acc2 frequency
transition point
Output frequency at which
Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz
U
0.0 Hz
A295
Acc1 to Acc2 frequency
transition point, 2
nd
motor
U
0.0 Hz
A096
Dec1 to Dec2 frequency
transition point
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
U
0.0 Hz
A296
Dec1 to Dec2 frequency
transition point, 2
nd
motor
U
0.0 Hz
A097
Acceleration curve selection Set the characteristic curve of
Acc1 and Acc2, five options:
00linear
01S-curve
02U-curve
03Inverse U-curve
04EL S-curve
U
00
A098
Deceleration curve selection Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097)
U
00
A101
[OI] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
U
0.00 Hz
A102
[OI] input active range end
frequency
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
U
0.0 Hz