C−9
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A103
[OI] input active range start
current
The starting point (offset) for
the current input range,
range is 0. to 100.%
U
20. %
A104
[OI] input active range end
current
The ending point (offset) for the
current input range,
range is 0. to 100.%
U
100. %
A105
[OI] input start frequency
select
Two options; select codes:
00…Use offset (A101 value)
01…Use 0Hz
U
00
−
a131
Acceleration curve constant Range is 01 to 10.
U
02
−
a132
Deceleration curve constant Range is 01 to 10.
U
02
−
A141
A input select for calculate
function
Seven options:
00…Operator
01…VR
02…Terminal [O] input
03…Terminal [OI] input
04…RS485
05…Option
07…Pulse train input
U
02
−
A142
B input select for calculate
function
Seven options:
00…Operator
01…VR
02…Terminal [O] input
03…Terminal [OI] input
04…RS485
05…Option
07…Pulse train input
U
03
−
A143
Calculation symbol Calculates a value based on the
A input source (A141 selects)
and B input source (A142
selects).
Three options:
00…ADD (A input + B input)
01…SUB (A input - B input)
02…MUL (A input * B input)
U
00
−
A145
ADD frequency An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
9
0.00 Hz
A146
ADD direction select Two options:
00…Plus (adds A145 value to
the output frequency
setting)
01…Minus (subtracts A145
value from the output
frequency setting)
U
00
−
a150
Curvature of EL-S-curve at
the start of acceleration
Range is 0 to 50%
U
10. %