C−14
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b034
Run/power ON warning time Range is,
0.:Warning disabled
1. to 9999.:
10~99,990 hrs (unit: 10)
1000 to 6553:
100,000~655,350 hrs (unit: 100)
U
0.
Hrs.
B035
Rotation direction restriction Three option codes:
00…No restriction
01…Reverse rotation is restricted
02…Forward rotation is restricted
U
00
−
b036
Reduced voltage start
selection
Set range, 0 (disabling the
function), 1 (approx. 6ms) to 255
(approx. 1.5s)
U
2
−
b037
Function code display
restriction
Seven option codes:
00…Full display
01…Function-specific display
02…User setting (and b037)
03…Data comparison display
04…Basic display
05…Monitor display only
U
04
−
b038
Initial display selection
000…Func. code that SET key
pressed last displayed.(*)
001~030…d001~d030 displayed
201…F001 displayed
202…B display of LCD operator
U
001
−
B039
Automatic user parameter
registration
Two option codes:
00…Disable
01…Enable
U
00
B040
Torque limit selection Four option codes:
00…Quadrant-specific setting
mode
01…Terminal-switching mode
02…Analog voltage input mode(O)
U
00
B041
Torque limit 1 (fwd/power) Torque limit level in forward
powering quadrant, range is 0 to
200%/no(disabled)
U
200 %
b042
B043
Torque limit 3 (rev/power) Torque limit level in reverse
powering quadrant, range is 0 to
200%/no(disabled)
U
200 %
B044
Torque limit 4 (fwd/regen.) Torque limit level in forward
regen. quadrant, range is 0 to
200%/no(disabled)
U
200 %
b045
Torque LAD STOP selection Two option codes:
00…Disable
01…Enable
U
00
b046
Reverse run protection Two option codes:
00…No protection
01…Reverse rotation is protected
U
01
−
b049
Dual Rating Selection
00… (CT mode) / 01… (VT mode)
U
00