C−15
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B050
Controlled deceleration on
power loss
Four option codes:
00…Trips
01…Decelerates to a stop
02…Decelerates to a stop with DC
bus voltage controlled
03…Decelerates to a stop with DC
bus voltage controlled, then
restart
U
00
−
B051
DC bus voltage trigger level
of ctrl. decel.
Setting of DC bus voltage to start
controlled decel. operation. Range
is 0.0 to 1000.0
U
220.0/
440.0
V
B052
Over-voltage threshold of
ctrl. decel.
Setting the OV-LAD stop level of
controlled decel. operation. Range
is 0.0 to 1000.0
U
360.0/
720.0
V
B053
Deceleration time of ctrl.
decel.
Range is 0.01 to 3600.0
U
1.0 sec
B054
Initial freq. drop of ctrl.
decel.
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
U
0.0 Hz
B060
Maximum-limit level of
window comparator (O)
Set range, {Min.-limit level (b061)
+ hysteresis width (b062)x2} to
100 %
(Minimum of 0%)
U
100. %
B061
Minimum-limit level of
window comparator (O)
Set range, 0 to {Max.-limit level
(b060) - hysteresis width
(b062)x2} % (Maximum of 0%)
9
0. %
B062
Hysteresis width of window
comparator (O)
Set range, 0 to {Max.-limit level
(b060) - Min.-limit level (b061)}/2 %
(Maximum of 10%)
9
0. %
B063
Maximum-limit level of
window comparator (OI)
Set range, {Min.-limit level (b064 +
hysteresis width (b065)x2} to
100 %
(Minimum of 0%)
9
100. %
B064
Minimum-limit level of
window comparator (OI)
Set range, 0 to {Max.-limit level
(b063) - hysteresis width
(b065)x2} % (Maximum of 0%)
9
0. %
b065
Hysteresis width of window
comparator (OI)
Set range, 0 to {Max.-limit level
(b063) - Min.-limit level (b064)}/2 %
(Maximum of 10%)
9
0. %
b070
Operation level at O
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no -
b071
Operation level at OI
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no -
b075
Ambient temperature setting Set range is,
-10~50 °C
9
40
°C
B078
Watt-hour clearance Two option codes:
00…OFF
01…ON (press STR then clear)
9
00 -
b079
Watt-hour display gain Set range is,
1.~1000.
9
1.
B082
Start frequency Sets the starting frequency for the
inverter output, range is 0.10 to
9.99 Hz
U
0.50 Hz
B083
Carrier frequency Sets the PWM carrier (internal
switching frequency), range is 2.0
to 15.0 kHz
U
2.0 kHz