C16
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B084
Initialization mode
(parameters or trip history)
Select initialized data, five option
codes:
00Initialization disabled
01Clears Trip history
02Initializes all Parameters
03Clears Trip history and
initializes all parameters
04Clears Trip history and
initializes all parameters and
EzSQ program
U
00
B085
Country for initialization Select default parameter values
for country on initialization, two
option codes:
00area A 01area B
U
00
B086
Frequency scaling conversion
factor
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.01 to 99.99
U
1.00
B087
STOP key enable Select whether the STOP key on
the keypad is enabled, three option
codes:
00Enabled
01Disabled always
02 Disabled for stop
U
00
B088
Restart mode after FRS Selects how the inverter resumes
operation when free-run stop
(FRS) is cancelled, three options:
00Restart from 0Hz
01Restart from frequency
detected from real speed of
motor (freq. matching)
02Restart from frequency
detected from real speed of
motor (active freq. matching)
U
00
b089
Automatic carrier frequency
reduction
Three option codes:
00Disabled
01Enabled, depending on the
output current
02Enabled, depending on the
heat-sink temperature
U
01 -
b090
Dynamic braking usage ratio Selects the rate of use (in %) of the
regenerative braking resistor per
100 sec. intervals, range is 0.0 to
100%.
0%: Function disabled
>0%: Enabled, per value
U
0.0 %
B091
Stop mode selection Select how the inverter stops the
motor, two option codes:
00DEC (decelerate to stop)
01FRS (free-run to stop)
U
00