C−22
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C047
Pulse train input/output
scale conversion
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in × (C047)
Set range is 0.01 to 99.99
9
1.00
C052
PID FBV output
high limit
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0 to
100%
U
100.0 %
C053
PID FBV output
low limit
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
U
0.0 %
C054
Over-torque/under-torque
selection
Two option codes:
00…Over-torque
01…Under-torque
U
00 -
C055
Over/under-torque level
(Forward powering mode)
Set range is 0 to 200%
U
100. %
C056
Over/under-torque level
(Reverse regen. mode)
Set range is 0 to 200%
U
100. %
C057
Over/under-torque level
(Reverse powering mode)
Set range is 0 to 200%
U
100. %
C058
Over/under-torque level
(Forward regen. mode)
Set range is 0 to 200%
U
100. %
C059
Signal output mode of
Over/under-torque
Two option codes:
00…During accel., decel. and
constant speed
01…During constant speed only
U
01 -
C061
Electronic thermal
warning level
Set range is 0 to 100%
Setting 0 means disabled.
U
90 %
C063
Zero speed detection level Set range is 0.0 to 100.0Hz
U
0.00 Hz
C064
Heat sink overheat
warning
Set range is 0 to 110 °C
U
100.
°C
C071
Communication speed Eight option codes:
03…2,400 bps
04…4,800 bps
05…9,600 bps
06…19,200 bps
07…38,400 bps
08…57,600 bps
09…76,800 bps
10…115,200 bps
U
05 baud
C072
Modbus address Set the address of the inverter on
the network. Range is 1 to 247
U
1.
−
C074
Communication parity Three option codes:
00…No parity
01…Even parity
02…Odd parity
U
00
−
C075
Communication stop bit Two option codes:
1…1 bit
2…2 bit
U
1 bit