C21
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C028
[AM] terminal selection
(Analog voltage output
0...10V)
11 programmable functions:
00Output frequency
01Output current
02Output torque
04Output voltage
05Input power
06Electronic thermal load ratio
07LAD frequency
10Heat sink temperature
11Output torque (with code)
13General output
16Option
U
07
[LAD]
C030
Digital current monitor
reference value
Current with digital current
monitor output at 1,440Hz
Range is 20%~200% of rated
current
9
Rated
current
A
C031
Output [11] active state Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
U
00
C032
Output [12] active state
U
00 -
C036
Alarm relay active state
U
01
C038
Output mode of low
current detection
Two option codes:
00During acceleration,
deceleration and constant speed
01During constant speed only
U
01
C039
Low current detection
level
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
U
INV rated
current
A
C040
Output mode of overload
warning
Two option codes:
00During accel., decel. and
constant speed
01During constant speed only
U
01
C041
Overload warning level Sets the overload warning signal
level between 0% and 200% (from 0
to two time the rated current of the
inverter)
U
Rated
current
x 1.15
A
C241
Overload warning level,
2
nd
motor
Sets the overload warning signal
level between 0% and 200% (from 0
to two time the rated current of the
inverter)
U
Rated
current
x 1.15
A
C042
Frequency arrival setting
for acceleration
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
U
0.0 Hz
C043
Frequency arrival setting
for deceleration
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
U
0.0 Hz
C044
PID deviation level Sets the allowable PID loop error
magnitude (absolute value), SP-PV,
range is 0.0 to 100%
U
3.0 %
C045
Frequency arrival setting
2 for acceleration
Set range is 0.0 to 400.0 Hz
U
0.00 Hz
C046
Frequency arrival setting
2 for deceleration
Set range is 0.0 to 400.0 Hz
U
0.00 Hz