C−20
Intelligent Terminal Functions
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C001
Input [1] function Select input terminal [1] function,
68 options (see next section)
U
00
[FW]
−
C002
Input [2] function Select input terminal [2] function,
68 options (see next section)
U
01
[RV]
−
C003
Input [3] function
[GS1 assignable]
Select input terminal [3] function,
68 options (see next section)
U
02
[CF1]
−
C004
Input [4] function
[GS2 assignable]
Select input terminal [4] function,
68 options (see next section)
U
03
[CF2]
−
C005
Input [5] function
[PTC assignable]
Select input terminal [5] function,
68 options (see next section)
U
09
[2CH]
−
C006
Input [6] function Select input terminal [6] function,
68 options (see next section)
U
18
[RS]
−
C007
Input [7] function Select input terminal [7] function,
68 options (see next section)
U
13
[USP]
−
C011
Input [1] active state Select logic conversion, two option
codes:
00…normally open [NO]
01…normally closed [NC]
U
00
−
C012
Input [2] active state
U
00
−
C013
Input [3] active state
U
00
−
C014
Input [4] active state
U
00
−
C015
Input [5] active state
U
00
−
C016
Input [6] active state
U
00
−
C017
Input [7] active state
U
00
−
C021
Output [11] function
[EDM assignable]
48 programmable functions
available for logic (discrete)
outputs
(see next section)
U
01
[FA1]
−
C022
Output [12] function
U
00
[RUN]
−
C026
Alarm relay function
48 programmable functions available
for logic (discrete) outputs
(see next section)
U
05
[AL]
−
C027
[EO] terminal selection
(Pulse/PWM output)
13 programmable functions:
00…Output frequency (PWM)
01…Output current (PWM)
02…Output torque (PWM)
03…Output frequency (Pulse train)
04…Output voltage (PWM)
05…Input power (PWM)
06…Electronic thermal load ratio
(PWM)
07…LAD frequency (PWM)
08…Output current (Pulse train)
10…Heat sink temperature (PWM)
12…General output (PWM)
15…Pulse train input monitor
16…Option(PWM)
U
07
−