EasyManuals Logo

IAI PCON-CB series User Manual

IAI PCON-CB series
538 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
4. Operation
4.2 Operation in Positioner Mode
4-16
ME0342-4B
(7) Threshold [%] :
Set the threshold value of the pressing torque in percent [%].
If the torque (load current) becomes larger than this setting value during pressing, the
detection signal is output. This feature is used to monitor the load current and judge
whether the operation is good or not in such an operation as press fitting in pressing.
(8) Positioning width [mm] :
For positioning in PIO patterns
(Note 1)
0 to 4, the positioning complete signal is output if the
remaining moving distance is entered within the zone set here.
For the pressing operation, the actuator should move in the same velocity and
acceleration/deceleration as those set for the normal positioning till it reaches the point set
in (2), and then starts pressing drive for the amount of data set in this section.
For PIO pattern 5, this item is not the complete signal output range against positioning
command. Just as it does in detection with a sensor, the applicable output signal (LS*)
should turn ON once the actuator gets in the range of the setting values regardless of the
indicated position number. PIO pattern 5 does not correspond to the pressing operation.
Make sure to set a value of the minimum positioning width or higher for the positioning
width.
(For 800 pulse encoder)
Min. Positioning Width = Lead Length / 800 (Number of Encoder Pulse) × 3
(For 8192 pulse encoder)
Min. Positioning Width = Lead Length / 8192 (Number of Encoder Pulse)
Note 1 PIO pattern: This is the operation pattern of Positioner mode.
Refer to [2.2.2 [1] PIO Patterns in Positioner Mode]
4.2 Operation in Positioner Mode
ME0342-4B 4-17
Reference
Output Range of LS Signal (Example of PIO pattern 5 and 7)
The figure below shows the position table and the position at which each of the LS
signals is turned ON. If the actuator passes any of the positioning bands in the
operation by another position number or manual operation in the servo OFF state,
the relevant LS signal is always turned ON.
(9) Zone + [mm] :
Set the coordinate value on the positive side at which position zone output signal PZONE is
turned ON. PZONE is set to ON in the zone between this value and the coordinate value on
the negative side set in (10).
(10) Zone - [mm] :
Set the coordinate value on the negative side at which position zone output signal PZONE
is turned ON.
150mm
75mm
0mm
LS2 is ON
150±5mm
LS1 is ON
75±5mm
LS0 is ON
0±5mm

Table of Contents

Other manuals for IAI PCON-CB series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IAI PCON-CB series and is the answer not in the manual?

IAI PCON-CB series Specifications

General IconGeneral
BrandIAI
ModelPCON-CB series
CategoryController
LanguageEnglish

Related product manuals