6. Parameter
6.1 Parameter
6-13 ME0342-4B
[9] Current Limit During Positioning Stop (Parameter No. 12)
No. Name Unit Input range
Default initial value setting
12
Current limit during
positioning stop
% 0 to 70
In accordance with actuator
By increasing the value, torque retention during stop will be increased.
There is normally no need to make changes. If significant external force is applied during the stop,
it is necessary to increase the set value.
[10] Current-limiting value during home return (Parameter No.13)
No. Name Unit Input Range Default factory setting
13
Current-limiting value
during home return
% 0 to 100 In accordance with actuator
The factory setting conforms to the standard specification of the actuator.
Increasing this setting will increase the home return torque.
Normally this parameter need not be changed. If the home return should be completed before
the correct position depending on the affixing method, load condition or other factors when the
actuator is used in a vertical application, the setting value must be increased.
[11] Select enable/disable pause input (Parameter No.15)
No. Name Unit Input Range Default factory setting
15
Select enable/disable
pause input
-
0 : Enabling,
1 : Disabling
0
This parameter defines whether the pause input signal is disabled or enabled.
If pause from PIO is not required, setting the parameter to “1” allows the actuator to be operated
without wiring of the pause signal input.