6. Parameter
6.1 Parameter
6-15 ME0342-4B
[14] Home Sensor Polarity (Parameter No. 18)
No. Name Unit Input range
Default initial value setting
18 Home sensor polarity - 0 to 2 In accordance with actuator
A parameter to select input polarity of the home sensor.
Home sensor is optional.
Set value Content
0
Standard specification
(home sensor not in use)
1 Input is a-contact
2 Input is b-contact
[15] Select enable/disable servo ON input (Parameter No.21)
No. Name Unit Input range
Default initial value setting
21
Select enable/disable servo
ON input
-
0 : Enabling
1 : Disabling
0
This parameter defines whether the servo ON input signal is disabled or enabled.
When the servo ON input signal is disabled, the servo is turned ON as soon as the controller
power is turned ON.
Set this parameter to “1” if servo ON/OFF is not provided by PIO signals.