6. Parameter
6.1 Parameter
6-43 ME0342-4B
[76] Monitoring Cycle (Parameter No. 113)
No. Name Unit Input range
Default initial value
setting
113 Monitoring cycle ms 1 to 60,000 1
Sets initial value
(Note 1)
of time cycle (sampling cycle) to obtain data when monitoring mode is
selected.
Data obtaining interval can be extended by increasing the value of this parameter.
The initial value is set at 1ms. Up to 60,000ms (60s) can be set in 1ms increments.
Record mode 1ms frequency setting 100ms frequency setting
2CH
Max. Obtainable Time 8.19s
Max. Obtainable Time 819s
4CH
Max. Obtainable Time 4.095s
Max. Obtainable Time 409.5s
8CH
Max. Obtainable Time 2.047s
Max. Obtainable Time 204.7s
Note 1 Sampling cycle can be changed by using PC software.
[77] Automatic Loadcell Calibration at Startup (Parameter No. 117)Pulse press only
No. Name Unit Input range
Default initial value
setting
117
Automatic Loadcell
Calibration at Startup
-
0: Not to Perform
1: To Perform
1
It is a parameter dedicated for the force sensor used pressing.
Set value Content
0
Not to Perform Automatic Loadcell Calibration
1
To Perform Automatic Loadcell Calibration (Default)
Refer to [4.2.8 Preparation for Operation in Force Sensor Pressing (Loadcell Calibration)]