14: CLOCK / CALENDAR INSTRUCTIONS
USERS MANUAL 14-7
Example: Sequential Start
This example demonstrates a program to turn outputs Q0 through Q2 on and off in sequence according to the chart below:
Internal relays are allocated as shown below.
Data registers are allocated as shown below. Comparison data must be set to data registers D20 through D39 in advance
using the program loader. For example, to enter decimal value “8” to data register D20, press the keys:
Comparison Data Hour Minute Comparison Data Hour Minute
Comparison Data 1 (8:30) M10 M11 Comparison Data 6 (13:10) M22 M23
Comparison Data 2 (8:40) M12 M13 Comparison Data 7 (13:20) M24 M25
Comparison Data 3 (8:50) M14 M15 Comparison Data 8 (17:00) M26 M27
Comparison Data 4 (12:00) M16 M17 Comparison Data 9 (17:30) M30 M31
Comparison Data 5 (13:00) M20 M21 Comparison Data 10 (18:00) M32 M33
Output Q0
ON
OFF
8:30
Comparison Data 1
12:00
Comparison Data 4
13:20
Comparison Data 7
18:00
Comparison Data 10
Output Q1
ON
OFF
8:40
Comparison Data 2
12:00
Comparison Data 4
13:10
Comparison Data 6
17:30
Comparison Data 9
Output Q2
ON
OFF
8:50
Comparison Data 3
12:00
Comparison Data 4
13:00
Comparison Data 5
17:00
Comparison Data 8
Second D12
Minute D11
Hour D10
Clock Readout Data
30
Minute D21
8
Hour D20
M11
M10
Comparison Data 1
(Turn output Q0 on)
MON
0
OR
E
D
LOD
10
40
Minute D23
8
Hour D22
M13
M12
Comparison Data 2
(Turn output Q1 on)
0
Minute D29
13
Hour D28
M21
M20
Comparison Data 5
(Turn output Q2 on)
0
Minute D35
17
Hour D34
M27
M26
Comparison Data 8
(Turn output Q2 off)
30
Minute D37
17
Hour D36
M31
M30
Comparison Data 9
(Turn output Q1 off)
0
Minute D27
12
Hour D26
M17
M16
Comparison Data 4
(Turn outputs Q0-Q2 off)
50
Minute D25
8
Hour D24
M15
M14
Comparison Data 3
(Turn output Q2 on)
8
MCS/R
2
BRD
10
Minute D31
13
Hour D30
M23
M22
Comparison Data 6
(Turn output Q1 on)
20
Minute D33
13
Hour D32
M25
M24
Comparison Data 7
(Turn output Q0 on)
0
Minute D39
18
Hour D38
M33
M32
Comparison Data 10
(Turn output Q0 off)