Table 31: EX Series Switch Environmental Tolerances (continued)
Environment Tolerance
Switch or
device SeismicTemperatureRelative HumidityAltitude
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Normal operation ensured in
relative humidity range of
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet
(3048 meters)
EX8216
Complies with Zone 4
earthquake
requirements as per
GR-63.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Nonoperating storage
temperature in shipping
container: –40° F (–40° C) to
158° F (70° C)
Normal operation ensured in
relative humidity range of
5% through 90%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
EX9204
Complies with Zone 4
earthquake
requirements as per
GR-63.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Nonoperating storage
temperature in shipping
container: –40° F (–40° C) to
158° F (70° C)
Normal operation ensured in
relative humidity range of
5% through 90%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
EX9208
Complies with Zone 4
earthquake
requirements as per
GR-63.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Nonoperating storage
temperature in shipping
container: –40° F (–40° C) to
158° F (70° C)
Normal operation ensured in
relative humidity range of
5% through 90%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
EX9214
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 41° F through
104° F (5° C through 40° C)
Normal operation ensured in
relative humidity range of
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
XRE200
NOTE: Install EX Series switches only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110–16,
110–17, and 110–18 of the National Electrical Code, ANSI/NFPA 70.
Related
Documentation
Clearance Requirements for Airflow and Hardware Maintenance for EX2200 Switches•
• Clearance Requirements for Airflow and Hardware Maintenance for EX3200 Switches
• Clearance Requirements for Airflow and Hardware Maintenance for EX3300 Switches
• Clearance Requirements for Airflow and Hardware Maintenance for EX4200 Switches
on page 72