Table 31: EX Series Switch Environmental Tolerances (continued)
Environment Tolerance
Switch or
device SeismicTemperatureRelative HumidityAltitude
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Normal operation ensured in
relative humidity range of
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet
(3048 meters)
EX8216
Complies with Zone 4
earthquake
requirements as per
GR-63.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Nonoperating storage
temperature in shipping
container: –40° F (–40° C) to
158° F (70° C)
Normal operation ensured in
relative humidity range of
5% through 90%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
EX9204
Complies with Zone 4
earthquake
requirements as per
GR-63.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Nonoperating storage
temperature in shipping
container: –40° F (–40° C) to
158° F (70° C)
Normal operation ensured in
relative humidity range of
5% through 90%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
EX9208
Complies with Zone 4
earthquake
requirements as per
GR-63.
Normal operation ensured in the
temperature range 32° F through
104° F (0° C through 40° C)
Nonoperating storage
temperature in shipping
container: –40° F (–40° C) to
158° F (70° C)
Normal operation ensured in
relative humidity range of
5% through 90%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
EX9214
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 41° F through
104° F (5° C through 40° C)
Normal operation ensured in
relative humidity range of
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet (3048
meters)
XRE200
NOTE: Install EX Series switches only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110–16,
110–17, and 110–18 of the National Electrical Code, ANSI/NFPA 70.
Related
Documentation
Clearance Requirements for Airflow and Hardware Maintenance for EX2200 Switches
Clearance Requirements for Airflow and Hardware Maintenance for EX3200 Switches
Clearance Requirements for Airflow and Hardware Maintenance for EX3300 Switches
Clearance Requirements for Airflow and Hardware Maintenance for EX4200 Switches
on page 72
65Copyright © 2015, Juniper Networks, Inc.
Chapter 6: Preparation Overview