Related
Documentation
Chassis Physical Specifications for EX4200 Switches on page 9•
• Rack-Mounting and Cabinet-Mounting Warnings on page 280
• Clearance Requirements for Airflow and Hardware Maintenance for EX4200 Switches
on page 72
• Mounting an EX4200 Switch on Two Posts in a Rack or Cabinet on page 160
• Mounting an EX4200 Switch on Four Posts in a Rack or Cabinet on page 163
• Mounting an EX4200 Switch in a Recessed Position in a Rack or Cabinet on page 166
Cabinet Requirements for EX4200 Switches
You can mount the switch in a cabinet that contains a 19-in. rack.
Cabinet requirements consist of:
•
Cabinet size
•
Clearance requirements
•
Cabinet airflow requirements
Table 34 on page 70 provides the cabinet requirements and specifications for the switch.
Table 34: Cabinet Requirements and Specifications for the Switch
Guidelines
Cabinet
Requirement
•
You can mount the switch in a cabinet that contains a 19-in. rack as defined in Cabinets, Racks,
Panels, and Associated Equipment (document number EIA-310–D) published by the Electronics
Industry Association (http://www.ecianow.org/standards-practices/standards/) .
•
The minimum cabinet size must be able to accommodate the maximum external dimensions of the
switch.
Cabinet size
•
The outer edges of the mounting brackets extend the width of the chassis to 19 in. (48.2 cm).
•
The minimum total clearance inside the cabinet is 30 in. (76.2 cm) between the inside of the front
door and the inside of the rear door.
Cabinet clearance
Copyright © 2015, Juniper Networks, Inc.70
EX4200 Switch Hardware Guide