If you are mounting the switch on a rack or cabinet with other equipment, or if you are
placing it on the desktop or floor near other equipment, ensure that the exhaust from
other equipment does not blow into the intake vents of the chassis.
Leave at least 24 in. (61 cm) both in front of and behind the switch. For service personnel
to remove and install hardware components, you must leave adequate space at the
front and back of the switch. NEBS GR-63 recommends that you allow at least 30 in.
(76.2 cm) in front of the rack or cabinet and 24 in. (61 cm) behind the rack or cabinet.
Related
Documentation
Rack Requirements for EX4200 Switches on page 69
Cabinet Requirements for EX4200 Switches on page 70
General Site Guidelines on page 66
Rack-Mounting and Cabinet-Mounting Warnings on page 280
Cooling System and Airflow in an EX4200 Switch on page 31
73Copyright © 2015, Juniper Networks, Inc.
Chapter 6: Preparation Overview

Table of Contents

Other manuals for Juniper EX4200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper EX4200 and is the answer not in the manual?

Juniper EX4200 Specifications

General IconGeneral
ModelEX4200
Switching Capacity128 Gbps
LayerLayer 2 and Layer 3
Form Factor1U
Throughput96 Mpps
Maximum VLANs4096
MAC Address Table Size16, 000
DRAM1 GB
Flash Memory1 GB
Forwarding Rate96 Mpps
JUNOS SoftwareYes
Ports24 or 48
StackingUp to 10 switches in a Virtual Chassis configuration
Power SupplyAC or DC
ManagementCLI, SNMP, J-Web
Input Voltage100-240 VAC or -48 VDC
Operating Temperature0°C to 45°C
RedundancyRedundant power supplies
Virtual Chassis TechnologyYes
Storage Temperature-40°C to 70°C
Humidity5% to 90% non-condensing

Related product manuals