When all requirements are met, perform the commissioning process for each communication
module as shown below.
The following description concerning the parametrisation refers to current
SIGMA CONTROL 2 software versions. Please contact KAESER SERVICE if the settings in
the machine deviate.
8.7.3.2 Commissioning the PROFIBUS module
Machine
1. Open the 8.2
<Communication – Com-Module>
menu.
2. Activate the
Com-Module Start
check box.
The communication module is activated. The system detects the communication module type
and displays it in the
Type
line.
3. Select the data exchange direction:
► SIGMA CONTROL 2 ⇆ Bus master (SIGMA CONTROL 2 sends process data and receives
control data):
Send/Receive
or
Master
: Set
Com-Module
.
► SIGMA CONTROL 2 → Bus master (SIGMA CONTROL 2 sends process data):
Send
or
Master
: Setting
SAM/JSON-RPC
.
For connection to a SIGMA AIR MANAGER:
Send/Receive
or
Master
: Set
Com-Module
.
4. Set the slave address (
Slave No.
:). The permissible address length is between 3 and 126. For
connection to a SIGMA AIR MANAGER: Slave address = compressor number + 102.
5. Set the required reaction in the event of a bus fault (see next chapter, “Reaction in a PROFI‐
BUS bus fault”).
6. Start the communication module with the set parameters. Activate the
Reset
check box.
The communication module is started with the set parameters.
7. Time-out at bus fault is activated.
Bus communication is now monitored.
The number behind
Status Counter (Run
) continuously changes during communication.
Reaction in a bus fault
Only for machines.
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
Parameters Factory setting Set value
Start td 15 s SIGMA AIR MANAGER without SIGMA AIR CONTROL
plus
30 s
SIGMA AIR MANAGER with SIGMA AIR CONTROL
plus
40 s
Tab. 66 Setting the
Starttd
parameter
SIGMA CONTROL 2 monitors the bus communication at log level (PROFIBUS). If there is a check
box behind
Communication error
, this monitoring in the
Send
mode can be switched off by deacti‐
vating the check box.
8 Initial Start-up
8.7 Setting the machine for master control operation
No.: 901700 10 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3
107

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet