1. Hold the RFID Equipment Card in front of the RFID reader.
Your user name and access level will be displayed.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
Log-in successful
Menu
Button to change password
Prompt, whether the password is to be changed
------------------------------
Name: E00019895
Level: 2
2. Press «Enter».
The access right is confirmed.
The RFID Equipment Card is damaged or lost?
➤ Manually enter the user name and password, see chapter 8.2.6.
8.2.5 Generating a password
In the event that your RFID Equipment Card is damaged or lost, you must manually log on to
SIGMA CONTROL 2. A password is also required to use KAESER CONNECT to log on at
SIGMA CONTROL 2 (see chapter 8.3).
Prerequisite for this is that you know your
■ Name
■ Password
You have noted your user name and stored it at a suitable location (see chapter 8.2.3). You now
generate a password at the SIGMA CONTROL 2. Note this generated password as well, and store
it a suitable location. If your RFID Equipment Card is damaged or lost, the card won't be necessary
to manually log on to SIGMA CONTROL 2 when you have these two pieces of information.
Precondition Any menu is displayed
Fig. 14 User log-in with RFID Equipment Card
8 Initial Start-up
8.2 Setting the controller
52
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3 No.: 901700 10 E