Machine number Start time [sec] Delay time [sec]
6
7
8
9
10
11
12
13
14
15
16
Tab. 63 Delay time for automatic restart
Precondition Access level 2 is activated.
1. Open the 5.3
<Configuration – Restart>
menu.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
5.3 Restart
Menu
Automatic restart
Automatic restart is deactivated
Delay 1s
Set/expiring delay time
2. Use «Up» or «Down» to select the
Delay
line.
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the delay time value.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
5.3 Restart
Menu
Automatic restart
Automatic restart is deactivated
Delay 10 s
Set/expiring delay time
5. Press the «Enter» key.
The setting is applied.
Result You have adjusted the delay tome for the restart after a power supply failure from 1 s to 10 s.
8 Initial Start-up
8.5 Machine start and machine stop
No.: 901700 10 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3
87

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet