Activating/deactivating the "Automatic restart" function
Precondition Access level 2 is activated.
1. Open the 5.3
<Configuration – Restart>
menu.
2. Use «Up» or «Down» to select the
Automatic restart
line.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
5.3 Restart
Menu
Automatic restart
Automatic restart is deactivated
Delay 10 s
Set/expiring delay time
3. Press «Enter».
The setting mode is active.
4. Press the «Up» key.
The check box is activated.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
5.3 Restart
Menu
Automatic restart
Active line with deactivated check box
Delay 10 s
Set/expiring delay time
5. Press the «Enter» key.
The setting is applied.
Result The "Automatic restart" function is activated.
8.5.4 Controlling machine from a remote location
If the machine is to be started and stopped from a remote control centre, provide the following set‐
tings:
Overview
Setting the load signal to remote mode
Setting the idle signal to remote mode
If necessary, activate the «Time control» key and configure the clock program (see chap‐
ter 8.5.1.2).
Activating the remote control
Press the «ON »key. The
On
LED lights green.
Two methods are available to start the machine remotely from a control centre:
8 Initial Start-up
8.5 Machine start and machine stop
88
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3 No.: 901700 10 E