8.7.3.5 Commissioning the DeviceNet module
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department.
1. Open the 8.2
<Communication – Com-Module>
menu.
2. Activate the
Com-Module Start
check box.
The communication module is activated. The system detects the communication module type
and displays it in the
Type
line.
3. Select the data exchange direction:
► SIGMA CONTROL 2 ⇆ Bus master (SIGMA CONTROL 2 sends process data and receives
control data):
Send/Receive
or
Master
: Set
Com module
.
► SIGMA CONTROL 2 → Bus master (SIGMA CONTROL 2 sends process data):
Send
or
Master
: Setting
SAM/JSON-RPC
.
4. Set the slave address (
Slave No.
:).
5. Set the required reaction in the event of a bus fault (see next chapter, “Reaction in a PROFI‐
BUS bus fault”).
6. Start the communication module with the set parameters.
7. Activate the
Reset
check box.
The communication module is started with the set parameters.
Communication with the bus master is running.
8. Time-out at bus fault is activated.
Bus communication is now monitored. The number behind
Status Counter (Run
) continuously
changes during communication.
Change the baud rate at the bus master during operation.
Activate the
Reset
check box to synchronise the communication module.
Reaction in a bus fault
Only for machines.
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
Parameters Factory setting Set value
Start td 15 s
Tab. 72 Setting the
Starttd
parameter
SIGMA CONTROL 2 monitors the bus communication at log level (SIGMA CONTROL 2). If there is
a check box behind
Communication error
, this monitoring in the
Send
mode can be switched off by
deactivating the check box.
In
Send/Receive
or
Master
modes, SIGMA CONTROL 2 can monitor:
Com-Module
the bus com‐
munication at user level. For this purpose, the bus master reads a value ("toggle bit") that changes
with every bus cycle and returns it without change. SIGMA CONTROL 2 returns a bus alarm if the
bit does not change for a time longer than set (
Timeout
). Activate the check box to enable monitor‐
ing.
8 Initial Start-up
8.7 Setting the machine for master control operation
No.: 901700 10 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3
111

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet