Parameters Factory setting Set value
Timeout 5 s
Monitoring Check box ☑ activated
Tab. 73 Setting the
Timeout
parameter
Enter the required settings, as described above.
8.7.3.6 Commissioning the PROFINET module
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department.
1. Open the 8.2
<Communication – Com-Module>
menu.
2. Activate the
Com-Module Start
check box.
The communication module is activated. The system detects the communication module type
and displays it in the
Type
line.
3. Select the data exchange direction:
► SIGMA CONTROL 2 ⇆ Bus master (SIGMA CONTROL 2 sends process data and receives
control data):
Send/Receive
or
Master
: Set
Com module
.
► SIGMA CONTROL 2 → Bus master (SIGMA CONTROL 2 sends process data):
Send
or
Master
: Setting
SAM/JSON-RPC
.
4. Enter the station name.
By means of the station name the bus master identifies SIGMA CONTROL 2.
5. Remove the check mark after
Use IP settings
to deactivate the IP settings. The IP address is
defined by the bus master and only shown on SIGMA CONTROL 2.
6. Set the required reaction in the event of a bus fault (see next chapter, “Reaction in a PROFI‐
BUS bus fault”).
7. Start the communication module with the set parameters:
8. Activate the
Reset
check box.
The communication module is started with the set parameters.
Communication with the bus master is running. The IP address defined by the bus master is
shown on SIGMA CONTROL 2.
9. Time-out at bus fault is activated.
Bus communication is now monitored. The number behind
Status Counter (Run
) continuously
changes during communication.
Reaction in a bus fault
Only for machines.
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
8 Initial Start-up
8.7 Setting the machine for master control operation
112
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3 No.: 901700 10 E

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet