The RFID read/write device transmits at a frequency of 13.56 MHz and is permitted for use in
EU member states.
3.1.2 Input/output module
The input/output module features:
Internal temperature monitoring
Internal undervoltage monitoring
LED indication of operational status
IOM 1
Input/Output Input/output module 1
Internal, in
the control
cabinet
available in
parallel on
both sides
External, into
the machine
interior
Digital input (DI), 24 VDC 4 10 2
Analogue input current (AII), 0–20 mA 1 2
Analogue input resistor (AIR), PT100 1 3
Digital output relay (DOR), 250 VAC, 8 A 8
Digital output transistor (DOT), 24 VDC, 0.5 A 2 1
Analogue output current (AOI), 0–20 mA
Tab. 12 IOM 1
3.1.2.1 Power supply specifications
Power is provided by the power supply unit within the machine.
Characteristic Value
Rated voltage (stabilised) [V DC] 24
Current consump‐
tion SIGMA CONTROL 2 with IOM 1 [A]
2.4
IOM ≙ Input/Output module
Tab. 13 Power supply specifications
3.1.2.2 Maximum cable lengths
Input/Output Cable length [m]
Analogue input current (AII),
Analogue input resistor (AIR)
Analogue output current (AOI)
30
Digital input (DI),
Digital output relay (DOR)
100
Digital output transistor (DOT) 30
Tab. 14 Cable lengths