KAESER SIGMA CONTROL 2 - Activating;deactivating the idle period “Venting period function; Autostart function

KAESER SIGMA CONTROL 2
184 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Variant A: Starting the machine with the input signal from the remote control centre.
Variant B: Starting the machine from the remote control centre in addition to a configured
ON/OFF clock program.
The machine can be started from the remote control centre even though the time control is ac‐
tivated and the ON/OFF program has selected OFF at this point in time.
8.5.4.1 Setting the load signal to remote mode
Precondition Electric connection via DI 1.04 – terminal -X15: 5+6 is made
Access level 2 is activated.
The operating mode is displayed.
1. Open the 5.5
<Configuration – External DI / AII signal>
menu.
2. Use «Up» or «Down» to select the
Load signal
line.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
5.5 External DI / AII signal
Menu
▶1 Current signal AII1.02
Load signal
active line
DI1.04
······························
Idle signal
DI1.09
3. Press the «DOWN» key.
The input
DI
has been selected.
4. Press «Enter».
The display for the currently set input flashes.
5. Select the input DI1.04 with the «Up» or «Down» key.
6. Press «Enter».
The setting is applied.
7. Press the «Right» key.
8. Press «Enter».
The check box assigned to the input flashes.
9. Press the «Up» key.
The check box is activated.
8 Initial Start-up
8.5 Machine start and machine stop
No.: 901700 10 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3
89