10. Press «Enter».
The setting is applied.
ok
is displayed.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
5.5 External DI / AII signal
Menu
▶1 Current signal AII1.02
Load signal
DI1.04 ok ☑
Active line with deactivated check box
······························
Idle signal
DI1.09
11. Press «Escape» repeatedly to leave this menu.
Result The load signal is set to remote operation.
8.5.4.2 Setting the idle signal to remote mode
Precondition The Load/Idle run valve is installed
Electric connection via DI 1.09 – terminal -X15: 11+12 is made
Access level 2 is activated.
The operating mode is displayed.
1. Open the 5.5
<Configuration – External DI / AII signal>
menu.
2. Use «Up» or «Down» to select the
Idle signal
line.
4 0 0 m b a r 0 8 : 1 5 A M 8 0 ° C
Header
5.5 External DI / AII signal
Menu
▶1 Current signal AII1.02
Load signal
DI1.04
······························
Idle signal
active line
DI1.09
3. Press the «DOWN» key.
The input
DI
has been selected.
4. Press «Enter».
The display for the currently set input flashes.
5. Select the input DI1.09 with the «Up» or «Down» key.
6. Press «Enter».
The setting is applied.
7. Press the «Right» key.
8. Press «Enter».
The check box assigned to the input flashes.
9. Press the «Up» key.
The check box is activated.
8 Initial Start-up
8.5 Machine start and machine stop
90
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3 No.: 901700 10 E

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet