Message Possible cause Remedy
0099 W
Switch T_S
1)
0100 W
FC service mode
activated
The frequency converter provided
by the customer is in service mode
Deactivate the service mode in
menu 10.1.1.3
0200 W
Change lube h ↑
Lubricating oil:
Maintenance interval has elapsed.
Change the lubricating oil.
0201 W
Change belt h ↑
V-belt:
Maintenance interval has elapsed.
Call KAESER SERVICE.
0202 W
Change filter h ↑
Inlet filter:
Maintenance interval has elapsed.
Replace the inlet filter.
0203 W
Change filter mat h ↑
Air filter:
Maintenance interval has elapsed.
Change the filter mat.
0204 W
Motor bearings lube h
Motor bearing of drive motor:
Maintenance interval has elapsed.
Re-lubricate the motor bearing of
drive motor.
0205 W
Check motor bearings
h ↑
Motor bearing of drive motor inspec‐
tion.
Check the motor bearing of drive
motor.
0206 W
Change motor
bearings h ↑
Motor bearing of drive motor:
Maintenance interval has elapsed.
Call KAESER SERVICE.
0207 W
Check motor bearings
encl. fan h ↑
Motor bearing of sound enclosure
fan motor:
Maintenance interval has elapsed.
Call KAESER SERVICE.
0208 W
Check control cabinet
fan h ↑
Motor bearing of control cabinet fan
motor:
Maintenance interval has elapsed.
Call KAESER SERVICE.
0209 W
Check FC fan h ↑
Motor bearing of frequency convert‐
er fan motor:
Maintenance interval has elapsed.
Call KAESER SERVICE.
0210 W
Annual maintenance
due
Last maintenance was 1 year ago. Carry out the necessary mainte‐
nance tasks and reset the corre‐
sponding maintenance interval
counters.
0211 W
Filter change
transmission venting h
Maintenance interval has elapsed Change the filter
0212 W
Electrical equipment h
Maintenance interval has elapsed Carry out the necessary mainte‐
nance tasks and reset the corre‐
sponding maintenance interval
counters.
0300 W
SD card write error
Fault while writing data to SD card. Call KAESER SERVICE.
10 Fault Recognition and Rectification
10.3 Interpreting warning messages
No.: 901700 10 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 2.5.3
159