286
Table of Functions
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
71 0h1547
P7 terminal
function
setting
P7 Define 7 Speed-L 9:Sp-H X/A O I/P p.78
8
Speed-M
p.78
9
Speed-H
p.78
11
XCEL-L
p.90
12
XCEL-M
p.90
13
RUN Enable
p.131
14
3-Wire
p.130
15
2nd Source
p.107
16
Exchange
p.178
17
Up
p.129
18
Down
p.129
20
U/D Clear
p.129
21
Analog Hold
p.77
22
I-Term Clear
p.136
23
PID Openloop
p.136
24
P Gain2
p.136
25
XCEL Stop
p.95
26
2nd Motor
p.177
34
Pre Excite
-
38
Timer In
p.188
40
dis Aux Ref
p.122
46
FWD JOG
p.128
47
REV JOG
p.128
49
XCEL-H
p.90
50
User Seq
p.112
51
Fire Mode
p.118
52
KEB-1 Select
p.154
54
TI
47
p.74
84 0h1554
Multi-function
input terminal
On filter
selection
Dl Delay Sel
P7 ~ P1
1
1111
48
O/A O I/P p.108
0
Disable(Off)
1 Enable(On)
85 0h1555
Multi-function
input terminal
On filter
DI On Delay 0-10000(ms) 10 O/A O I/P p.108
86
0h1556
Multi-function
DI Off Delay
0-10000(ms)
3
O/A
O
I/P
p.108
47
Displayed when P5 is selected on Px terminal function.(Only Standard I/O)