EasyManua.ls Logo

LSIS LSLV-S100 - Page 4

LSIS LSLV-S100
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iv
Safety Information
Do not modify the interior workings of the inverter. Doing so will void the warranty.
The inverter is designed for 3-phase motor operation. Do not use the inverter to operate a single
phase motor.
Do not place heavy objects on top of electric cables. Doing so may damage the cable and
result in an electric shock.
Note
Maximum allowed prospective short-circuit current at the input power connection is defined in IEC
60439-1 as 100 kA. Depending on the selected MCCB, the LSLV-S100 Series is suitable for use in circuits
capable of delivering a maximum of 100 kA RMS symmetrical amperes at the drive's maximum rated
voltage. The following table shows the recommended MCCB for RMS symmetrical amperes.
Remarque
Le courant maximum de court-circuit présumé autorisé au connecteur d’alimentation électrique est
défini dans la norme IEC 60439-1 comme égal à 100 kA. Selon le MCCB sélectionné, la série LSLV-S100
peut être utilisée sur des circuits pouvant fournir un courant RMS symétrique de 100 kA maximum en
ampères à la tension nominale maximale du variateur. Le tableau suivant indique le MCCB
recommandé selon le courant RMS symétrique en ampères.
Working Voltage
UTE100(E/N)
UTS150(N/H/L)
ABS33c
ABS53c
ABS63c
ABS103c
240V(50/60Hz)
50/65 kA
65/100/150 kA
30 kA
35 kA
85 kA
480V(50/60Hz) 25/35 kA 35/65/100 kA 7.5 kA 10 kA 10 kA 26 kA

Table of Contents

Other manuals for LSIS LSLV-S100

Related product manuals