32
Installing the Inverter
Function
Label
Name
Description
Output voltage: 010V
Maximum output voltage/current: 12V/10mA
Output current: 020mA
Maximum output current: 24mA
Factory default output: Frequency
TO Pulse Output
Sends pulse signals to external devices to provide a
single output value from the inverter of either:
output frequency, output current, output voltage,
or DC voltage.
Output Signal Specifications:
Output frequency: 032kHz
Output voltage: 012V
Factory default output: Frequency
(In case of Standard I/O, Pulse output TO and Multi-
function output Q1 share the same terminal. Set
the OU.33Q1 Define to 38(TO).)
When connecting to a pulse between the S100
inverters,
Multiple I/O< -> Multiple I/O : Connect to TO
-> TI, CM -> CM
Standard I/O <-> Standard I/O : Connect to
Q1 -> P5, EG -> CM
Multiple I/O <-> Standard I/O : Do not
support.
Digital output
Q1
Multi-functional
(open collector)
DC 26V, 100mA or less
Factory default output: Run
EG Common
Common ground contact for an open collector
(with external power source)
24
External 24V
power source
Maximum output current: 150mA
A1/C1/B1 Fault signal output
Sends out alarm signals when the inverters safety
features are activated (AC 250V <1A, DC 30V < 1A).
Fault condition: A1 and C1 contacts are
connected (B1 and C1 open connection)
Normal operation: B1 and C1 contacts are
connected (A1 and C1 open connection)
Communication
S+/S-/SG RS-485 signal line
Used to send or receive RS-485 signals. Refer to 7
RS-485 Communication Features on page 229 for
more details.