Installing the Inverter
Preinsulated Crimp Terminal Connectors (Bootlace Ferrule) .
Use preinsulated crimp terminal connectors to increase reliability of the control terminal wiring.
Refer to the specifications below to determine the crimp terminals to fit various cable sizes.
P/N
Cable Spec.
Dimensions (inches/mm)
Manufacturer
AWG
mm
2
L*
P
d1
D
CE002506
26 0.25
10.4
0.4 / 6.0
0.04 / 1.1 0.1 / 2.5
JEONO
(Jeono Electric,
http://www.jeono.com/
)
CE002508
12.4
0.5 / 8.0
CE005006
22
0.50
12.0
0.45 / 6.0
0.05 / 1.3
0.125 / 3.2
CE007506
20
0.75
12.0
0.45 / 6.0
0.06 / 1.5
0.13 / 3.4
* If the length (L) of the crimp terminals exceeds 0.5” (12.7mm) after wiring, the control terminal
cover may not close fully.
To connect cables to the control terminals without using crimp terminals, refer to the following
illustration detailing the correct length of exposed conductor at the end of the control cable.
Note
While making wiring connections at the control terminals, ensure that the total cable length does
not exceed 165ft (50m).
Ensure that the length of any safety related wiring does not exceed 100ft (30m).
Ensure that the cable length between an LCD keypad and the inverter does not exceed 10ft
(3.04m). Cable connections longer than 10ft (3.04m) may cause signal errors.
Use ferrite material to protect signal cables from electro-magnetic interference.
Take care when supporting cables using cable ties, to apply the cable ties no closer than 6 inches