EasyManua.ls Logo

Omron SYSDRIVE 3G3FV - Page 224

Omron SYSDRIVE 3G3FV
400 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-50
D PID Control Settings
Parameter Display name Setting Units Default
Valid access levels
number
py
g
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b5-01 PID Mode 0 to 4 --- 0 Advanced
This parameter cannot be changed during operation.
Set value Contents
0 PID disabled
1 PID enabled (Deviation signal is put through derivative control.)
2 PID enabled (Feedback signal is put through derivative control.)
3 PID enabled. (Frequency reference and PID control/deviation signal are put through
derivative control.)
4 PID enabled. (Frequency reference and PID control/feedback signal are put through
derivative control.)
Note 1. To
enable PID control, set 1 through 4. (Normally 2 or 4 is used for measured-value derivative
PID control.)
Note 2. If
the target speed of the application (e.g., tension control) is rather
clear and PID control is
required for fine tuning, set 3 or 4 for frequency reference and PID control.
Setting Target Values for PID Control
The following guidelines can be used to select target values for PID Control.
c Contents
Frequency reference input,
voltage: Terminal 13
The frequency source selected for parameter b1-01 is used as the
target value.
Note 1. If
the PID control target value is not set for a multi-function ana
-
lo
g
input or fre
q
uenc
y
reference
(
current
)
selection
(
H3-05
,
Setting via Digital Operator
log
in ut
or
frequency
reference
(current)
selection
(H3-05
,
H3-09), then the setting of b1-01 is used automatically.
Note 2. Frequency references 2 to 8 and the inching reference are
enabled regardless of the setting of b1 01
Option frequency reference
ena
bl
e
d
regar
dl
ess o
f
t
h
e sett
i
ng o
f
b1
-
01
.
Note 3. Operation
will be clearer if o1-03 is set to 1 (% unit) when set
-
ting from a Digital Operator.
Multi-function analog input:
Terminal 16
Set C for the function selection of multi-function analog input terminal
16 (H3-05) to select the PID target value.
Frequency reference, current:
Terminal 14
Set C for the function selection of frequency reference (current)
terminal 14 (H3-09) to select the PID target value.
Note When using different input signals for frequency reference and PID control, set the PID target
value to either a multi-function analog input or the frequency reference (current).
Setting Feedback Values for PID Control
The following guidelines can be used to select feedback values for PID Control.
c Contents
Multi-function analog input:
Terminal 16
Set B for the function selection of multi-function analog input terminal
16 (H3-05) to select the PID feedback value.
Frequency reference, current:
Terminal 14
Set B for the function selection of frequency reference (current)
terminal 14 (H3-09) to select the PID feedback value.
Note 1. Use the gain and bias settings for the analog inputs to adjust the feedback value.
Advanced Operation Chapter
6

Table of Contents

Related product manuals