7-40
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
H3-08
Signal
selection:
terminal 14
0:
0 to +10 V (Always cut
jumper wire J1)
1:
0 to
±10 V (Always cut
j i J1)
0 to 2
2 NO A A A A 5-6
T
erm 14
Signal
(y
jumper wire J1)
2:
4 to 20 mA
H3-09
Selection:
T
erminal 14
Set as for H3-05.
Note:
Cannot be set to 0. The
1 to 1F
1F NO A A A A 5-5,
6-93
T
erminal 14
Sel
Note:
Cannot
be
set
to
0
.
The
1F function will become
“frequency reference.”
H3-10
Gain: T
er-
minal 14
Sets the input gain (level) when
terminal 14 is 10 V (20 mA).
Th t t i th f ll i
0.0 to
1000.0
100.0 OK A A A A 5-7
T
erminal 14
Gain
()
The contents in the following
table are taken as 100%.
H3-11
Bias: T
ermi-
nal 14
Sets the input gain (level) when
terminal 14 is 0 V (4 mA).
Th t t i th f ll i
–100.0
to
100 0
0.0 OK A A A A 5-7
T
erminal 14
Bias
()
The contents in the following
table are taken as 100%.
+100.0
H3-12
Analog in
-
put filter
time con
-
stant
Sets terminals 13, 14, 16 to
primary delay filter time
constant, in seconds units.
Note: Ef
fective for noise control
0.00 to
2.00
0.00 NO A A A A 5-8
Filter A
vg
Time
Note: Ef
fective
for
noise
control
etc.
Parameter Lists Chapter
7

Table of Contents