MANUAL NUMBER 160339
REVISION 09SEPT04 PAGE 15
PERIODIC MAINTENANCE
PRE-TRIP
Verify the Protection Panel ‘SYSTEM OK’ lamp is on solid green
EVERY 3000 MILES OR MONTHLY (whichever occurs first)
General
Verify neither the protected equipment nor the hazard has changed
Verify no obvious physical damage or condition exists that might prevent system operation
Protection Panel
Verify all warning lamps and the audible alarm are operational by pressing the
‘TEST/RESET’ button
Manual Activation Switch
Verify tamper seal is intact and access to switch is unobstructed
Fire Detectors
Optical
Verify status lamp on the detector face is on solid green
Verify nothing is blocking the detector’s field of view
Verify the windows on the face of the detector are free of excess contamination (dirt,
oil, grease, etc) - if necessary, clean using water soaked non-abrasive towel
Linear Thermal
Verify there is no obvious physical damage and that unit is free of excess
contamination (dirt, oil, grease, etc) - if necessary, clean using water soaked non-
abrasive towel
Verify mounting is secure and taught
Electrical Harness
Verify electrical connectors and electrical wiring have no visible damage and all connectors
are securely seated
Extinguisher & Distribution System
Verify the extinguisher pressure gauge pointer is in the green arc at room temperature
Verify distribution piping and nozzles are intact and unobstructed and that nozzle blow-off
caps are in place