Installation manual
42
RKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62576-1 – 10.2010
F Option setup
00 Pump operation stop 0
(enabled)
0/1 1
01 Space cooling permission temperature 20 10~35 1 °C
02 Bottom plate heater ON temperature 3 3~10 1 °C
03 Bottom plate heater hysteresis 5 2~5 1 °C
04 Functionality of X14A
(b)
. 1 0/1
Underfloor heating screed dry-out program
05 Action number selection 1 1~20 1
06 Heating set point of selected action number [F-05] 25.0
(d)
15~55 1 °C
07 Time of selected action number [F-05] 0
(d)
0~72 12 hour
08 Underfloor heating screed dry-out program enabled/
disabled
0 (OFF) 0/1 1
09 Latest action number executed
0
0~21
(Read only)
0—
(a) The storage and reheat function is only applicable in case [4-03]=4 or 5.
(b) Only possible to modify the first 3 minutes after power ON.
(c) The default value is only an indication as it is depending on the connected outdoor unit.
(d) For all action numbers of [F-05].
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value

Table of Contents

Other manuals for Rotex RKHBH016BB3V3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex RKHBH016BB3V3 and is the answer not in the manual?

Rotex RKHBH016BB3V3 Specifications

General IconGeneral
BrandRotex
ModelRKHBH016BB3V3
CategoryHeat Pump
LanguageEnglish

Related product manuals