Table 15: Starting and stopping safety function
Start starts the safety function.
Stop stops the safety function.
DANGER
H
azard due to lack of effectiveness of the protective device
Persons and parts of the body to be protected may not be recognized in case of non-
observance.
If the configuration is verified, the device automatically starts the safety function after
switching on the voltage supply.
If the configuration is not verified, the safety laser scanner may not be operated as a
protective device. You can start the safety function manually to test the safety laser
scanner and the configuration. The test operation has a time limit.
b
Only operate the safety laser scanner as a protective device if the configuration is
verified.
7.17 Reports
You can show a device’s data with a report. You have the option of saving and archiving
t
hese data as a PDF.
Safety Designer creates a report as soon as you click on Report in the navigation. If after
configuration changes you click on Update, you will receive an updated report.
National and international standards promote or recommend specific data and the per‐
son responsible for it. The required data is included in the report.
1. Print the report.
2. Write down the responsible person on the report.
3. Archive the report.
CONFIGURATION 7
8021913/15ZW/2019-11-14 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – EFI-pro
113
Subject to change without notice