Operating
7.8 Alarms
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
113
The level alarm is the most common. Use this alarm to warn you when the process is in
danger of being upset due to high or low levels. Generally, the four alarms used are Hi, Hi-
Hi, Lo, and Lo-Lo.
Set the common parameters
You must know the details of your application and substitute the values for the sample
values provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Sensor Mode (2.1.3.)
Global *Level Operation = *Level
Material (2.1.6.)
Global Liquid Material = *Liquid
Response Rate (2.3.4.)
Global Medium Maximum Process Speed = *Medium (1.0
Transducer (2.1.5.)
Global XPS-10 Transducer = XPS-10 (single-point preset)
Units (2.1.1.) (Page 162)
Empty (2.2.4.)
Global 1.8 Empty = 1.8 m
1
This example assumes a base, single measurement unit. If your unit has optional dual-
point software installed, then some parameters are indexed by two level points.