EasyManua.ls Logo

Siemens HydroRanger 200 HMI - Parameter access (R43,998-R46,999)

Siemens HydroRanger 200 HMI
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications
C.26 Pump starts (R41,470-R41,475)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
333
C.26
Pump starts (R41,470-R41,475)
The number of pump starts for the referenced pump relay.
This value comes from parameter Pump Starts (3.2.9.4.) (Page 260).
C.27
Parameter access (R43,998-R46,999)
Parameter values are given as integers in the range of registers from R44,000 to R44,999.
The last three numbers of the register correspond to the parameter number.
Parameter register #
Format register #
Parameter
44,000 46,000 Write Protection (5.1.)
(Page 271)
44,001 46,001 Sensor Mode (2.1.3.)
(Page 163)
44,002
46002
Material (2.1.6.) (Page 165)
...
...
...
44,999 46,999 Master Reset (3.2.3.)
(Page 254)
Usually, the parameters are all
read / write
.
Note
Parameters Write Protection (5.1.) (Page 271) and Master Reset (3.2.3.) (Page 254) are
Read only
.
Master Reset (3.2.3.) (Page 254) cannot be used via Modbus.
See Data types (Page 339) for a description of the types associated with different
parameters.
Each parameter register has a corresponding format register that holds the format
information required to interpret the value. See Format words (Page 337).

Table of Contents

Related product manuals