HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
91
Operating
7
This chapter provides details on the general operation and functionality of the device. For
instructions on the use of the device LCD and local push buttons, refer to The local display
(Page 51)and LCD Menu Structure (Page 371).
Power up display
Single-point model
Preset to display distance from the face of the transducer to the material
Transducer selection is preset for the XPS-10
Empty distance is preset to 5 m (meters)
Dual-point model
Starts in an OFF state and does not take Level measurements.
To set up measurement, the quick start parameters must be configured.
See Quick Start Wizards (Page 59)
Note
The number of points is an order option and is set by the factory. On a single
-point model,
the index for Sensor
Mode (2.1.3.) is Global. On a dual-point model, the index for
Sensor Mode (2.1.3.)
(Page 163) is 1 or 2. For the index number location, see The local
display
(Page 51).
7.1
Single-point models
The device starts in
Distance
mode with the transducer preset for the XPS-10 and an empty
distance of 5 meters. Change the following parameters to reflect your application
parameters.
Parameter
Index
Value/mode
Description
Sensor mode (2.1.3.) (Page 163)
Global
*Level
Operation = *Level
Material (2.1.6.) (Page 165) Global Liquid Material = *Liquid
Response rate (2.3.4.) (Page 174) Global Medium Maximum Process Speed=
*Medium (1.0 m/ min)
Transducer (2.1.5.) (Page 164) Global XPS-15 Read only = XPS-15
Units (2.1.1.) (Page 162)
Global
Meters
Units = Meters
Empty (2.2.4.) (Page 170)
Global
12
Empty = 12 m
Span (2.2.2.) (Page 169)
Global
10
Span = 10 m