Technical data
11.7 Construction
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
299
11.7
Construction
Enclosure
Wall mount 240 mm (9.5 inch) x 175 mm (6.9 inch). Width
dimension includes hinges.
Type 4X / NEMA 4X / IP65
1
Polycarbonate
Panel mount 278 mm (10.93 inch) x 198 mm (7.8 inch),
width dimension includes flange.
Type 3 / NEMA 3 / IP54
Polycarbonate
Display
Backlit HMI LCD display
Cable
Using a co-axial cable with the device is NOT
recommended. If it is really necessary to use
such cable, see Upgrading, co-axial trans-
ducer extension (Page 354) for instructions.
Split cables: transducer cable to be two cop-
per conductors, twisted shielded wire, 300
Vrms,
0.324 ... 0.823 mm
2
(22 ... 18 AWG), nominal
capacitance between adjacent conductors @
1 kHz = 62.3 pF/m (19 pF/ft), nominal capaci-
tance between conductor and shield @ 1 kHz
= 108.3 pF/m (33 pF/ft) (Belden
2
8760 is ac-
ceptable).
mA output cable to be two copper conductors,
twisted shielded wire, 300 Vrms,
0.324 ... 0.823 mm
2
(22 ... 18 AWG), nominal
capacitance between adjacent conductors @
1 kHz = 62.3 pF/m (19 pF/ft), nominal capaci-
tance between conductor and shield @ 1 kHz
= 108.3 pF/m (33 pF/ft) (Belden
2
8760 is ac-
ceptable).
365 m maximum
Weight
Wall mount: 1.22 kg (2.68 lb)
Panel mount: 1.35 kg (2.97 lb)
1
For watertight applications, use only approved, suitable-sized hubs in the enclosure’s
conduit holes.
2
Belden is a registered trademark of Belden Wire & Cable Company.