Operating
7.9 Pump control
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
123
Set the Relay OFF Setpoint
OFF Setpoint (2.8.1.6.)
1 1.3 m Sets the three setpoints for the
pump relays.
OFF Setpoint (2.8.1.6.)
(Page 197)
2 1.3 m
OFF Setpoint (2.8.1.6.)
3 1.3 m
Set relays to Service Ratio Duty Assist
Relay Function (2.8.1.4.)
1 Service Ratio Duty Assist Sets the pump relays (Relays 1,
2, and 3) to Service Ratio Duty
Assist.
Relay Function (2.8.1.4.)
2 Service Ratio Duty Assist
Relay Function (2.8.1.4.)
3 Service Ratio Duty Assist
Service Ratio (2.8.1.12.)
1 25 Sets the ratio to:
• 25% – Pump 1
• 50% – Pump 2
• 25% – Pump 3
Service Ratio (2.8.1.12.)
2 50
Service Ratio (2.8.1.12.)
3 25
Set the Relay ON Setpoints
ON Setpoint (2.8.1.5.)
1 0.4 m Sets the three setpoints for the
pump relays. The first cycle will
use these setpoints. Subse-
quent cycles rotate the set-
points among the pumps.
ON Setpoint (2.8.1.5.)
2 0.3 m
ON Setpoint (2.8.1.5.)
3 0.2 m
Set the Relay OFF Setpoints
OFF Setpoint (2.8.1.6.)
(Page 197)
1 1.3 m Sets the three setpoints for the
pump relays.
OFF Setpoint (2.8.1.6.)
2 1.3 m
OFF Setpoint (2.8.1.6.)
3 1.3 m