7.10 Rake (screen) control
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
133
Setting common parameters
Prerequisite:
Substitute the details of your application in place of the sample values provided. If you are
bench testing the unit, set your test values to be the same as the sample values.
Sensor mode (2.1.3.)
Global Dual-point Difference
Operation=Differential
Material (2.1.6.)
(Page 165)
Global *Liquid (Page 165) Material=Liquid
Response rate (2.3.4.)
1 & 2 *Medium (1.0 m/min)
Max. Process Speed=Medium
Transducer (2.1.5.)
1 & 2 XPS-10 (single-point pre-
Transducer=XPS-10
Units (2.1.1.)
Global 1 Units=Meters
Empty (2.2.4.)
2 2.2 Empty=2.2 m
Span (2.2.2.)
(Page 169)
Set Relay 1 (Operate Rake)
Level Source (2.8.1.2.)
1 Difference or average Starts the rake when the
difference between the two
levels rises above 0.4 m and
stops the rake when the
difference falls below 0.1 m.
Relay Function (2.8.1.4.)
1 Fixed Duty Assist
ON Setpoint (2.8.1.5.)
1 0.4
OFF Setpoint (2.8.1.6.)
(Page 197)
1 0.1