Operating
7.10 Rake (screen) control
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
133
7.10.2
Setting common parameters
Prerequisite:
Substitute the details of your application in place of the sample values provided. If you are
bench testing the unit, set your test values to be the same as the sample values.
Parameter
Index
Mode/Value
Description
Sensor mode (2.1.3.)
(Page 163)
Global Dual-point Difference
(Page 163)
Operation=Differential
Material (2.1.6.)
(Page 165)
Global *Liquid (Page 165) Material=Liquid
Response rate (2.3.4.)
(Page 174)
1 & 2 *Medium (1.0 m/min)
(Page 174)
Max. Process Speed=Medium
Transducer (2.1.5.)
(Page 164)
1 & 2 XPS-10 (single-point pre-
set)
Transducer=XPS-10
Units (2.1.1.)
(Page 162)
Global 1 Units=Meters
Empty (2.2.4.)
(Page 170)
1
1.8
Empty=1.8 m
2 2.2 Empty=2.2 m
Span (2.2.2.)
(Page 169)
1
1.4
Span=1.4 m
2
1.4
Span=1.4 m
3
1.4
Max Differential=1.4 m
7.10.3
Set Relay 1 (Operate Rake)
Parameter
Index
Mode/value
Description
Level Source (2.8.1.2.)
(Page 194)
1 Difference or average Starts the rake when the
difference between the two
levels rises above 0.4 m and
stops the rake when the
difference falls below 0.1 m.
Relay Function (2.8.1.4.)
(Page 195)
1 Fixed Duty Assist
ON Setpoint (2.8.1.5.)
(Page 197)
1 0.4
OFF Setpoint (2.8.1.6.)
(Page 197)
1 0.1