Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
167
8.6.1.12
Number of long shots (2.1.12.)
Sets the number of long shots to be fired (and results averaged) per transmit pulse.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0 to 200
Preset: 5
Response rate (2.3.4.) (Page 174)
Related
Number of short shots (2.1.11.) (Page 166)
Long shot frequency (2.1.8.) (Page 165)
Short shot duration (2.1.9.) (Page 166)
This value is automatically altered by Response rate (2.3.4.) (Page 174)
8.6.1.13
Shot synchro (2.1.13.)
Enables the System Sync on the terminal block.
Index
Global
Options
Not required
*Synchronized level monitors
Use this if another level measurement system is mounted nearby, and wired together on the
Sync terminal.
8.6.1.14
Scan delay (2.1.14.)
Adjusts the delay between measurements from transducer points, in seconds. Dual-point
model only.
Index
Global
Values
Range: 0 to 60 seconds
Preset: 5
Altered by
Response rate (2.3.4.) (Page 174)
Related
Sensor mode (2.1.3.) (Page 163)
This feature may only be used to adjust the delay before the next point is scanned. This
value is automatically altered when Response Rate (2.3.4.) (Page 174) is altered.