Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
174 Operating Instructions, 06/2018, A5E36281317-AC
8.6.3.4
Response rate (2.3.4.)
Determines the level change reaction.
Index
Transducer
Options
Slow (0.1 m/min)
*Medium (1.0 m/min)
Fast (10.0 m/min)
Alters
LOE timer (2.4.2.) (Page 177)
Fill rate/minute (2.3.2.) (Page 173)
Empty rate/minute (2.3.3.) (Page 173)
Filling indicator (2.3.9.) (Page 176)
Emptying indicator (2.3.10.) (Page 176)
Rate filter (2.3.5.) (Page 175)
Fuzz filter (2.11.5.6.) (Page 236)
Echo lock window (2.11.5.5.) (Page 235)
Scan delay (2.1.14.) (Page 167)
Number of long shots (2.1.12.) (Page 167)
Related
Material level (2.4.5.) (Page 178)
Fail-safe advance (2.4.6.) (Page 179)
Pump by rate (2.8.1.8.) (Page 198)
Rate filter time (2.3.6.) (Page 175)
Rate filter distance (2.3.7.) (Page 175)
Rate (2.3.) (Page 172)
Echo lock (2.11.5.4.) (Page 235)
Measurement verification (2.11.5.) (Page 233)
Shot synchro (2.1.13.) (Page 167)
Shot delay (2.1.16.) (Page 168)
Scan time (2.1.15.) (Page 168)
Use a setting just fast enough to keep up with your process. Slower settings provide higher
accuracy. Faster settings allow for more level fluctuations.