Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
181
Current output function (2.5.3.)
Alters the mA output/measurement relationship.
OFF
Level, differential, or average
• mA output allocation (2.5.4.) (Page 181)
• Milliamp output (2.5.9.) (Page 182)
Sensor mode (2.1.3.) (Page 163)
mA output allocation (2.5.4.)
Sets the input source from which the mA output is calculated.
Average of readings from Point 1 and Point 2
Current output function (2.5.3.) (Page 181)
Enter the point number the mA output is based on. This value depends on whether Current
Output Function (2.5.3.) (Page 181) is set as transducer or mA input.
For a single-point device, if Current Output Function (2.5.3) (Page 181) uses a transducer,
parameter mA Output Allocation (2.5.4) can only be altered if Sensor Mode (2.1.3.)
(Page 163) is set for DPD or DPA.
Parameter mA Output Allocation (2.5.4.) can be set to a particular point or range of points.
When set to a range of points, the mA output will be the average of the readings from all in
service transducers in the range. Out-of-service transducers will be ignored.