Commissioning
6.3 RUN mode
HydroRanger 200 HMI
54 Operating Instructions, 06/2018, A5E36281317-AC
6.3.3
Auxiliary reading
Measurement View 2 displays an Auxiliary Reading area in addition to the Primary Reading.
The Auxiliary Reading can display additional information that you choose.
Setting a specific Auxiliary Reading
To set the value initially displayed in the Auxiliary Reading, use Default auxiliary reading
(2.12.7.) (Page 239).
The Auxiliary Reading value that you choose is automatically synchronized with the Primary
Reading value as the display scrolls through the Level Points. For example, if the Primary
Reading is
Level
and you have chosen
Volume
for the Auxiliary Reading, the device will
always show Level (in the Primary) and Volume (in the Auxiliary) for the same Level Point.
The Level Point is shown in Measurement Mode Display as caption number 6 on the
local
display diagram (Page 51).
Temporarily overriding the Auxiliary Reading
You can temporarily override the value displayed in the Auxiliary Reading by pressing the
arrow in RUN mode. This allows you to see values in the Auxiliary Reading area that are not
associated with a particular Level Point.
For example, you may have configured the Primary Reading to display Flow, and the
Auxiliary Reading to display Head. If you want to see what the milliamp outputs are, you can
press the
arrow. This first press of arrow will temporarily replace the Auxiliary Reading
with milliamp output #1. Press the
arrow again to display milliamp output #2, and press it
a third time to see the milliamp input.
The device will continue to display your selected temporary value until the next power cycle.
After a power cycle, the device will show the default auxiliary reading [see Default auxiliary
reading (2.12.7.) (Page 239) ] when you display Measurement View 2.
6.3.4
Multiple readings
During
differential
or
average
operation [Sensor Mode (2.3.1.) (Page 163) = Dual-Point
Difference/Dual-Point Average (Page 163) ], Measurement Views 1 and 2 scrolls
sequentially through Point Numbers 1, 2, and 3. Point 3 is the difference between (or
average of) Points 1 and 2.
Changing number scrolling speed
Parameter
Value
Description
Display Delay (2.12.8.)
(Page 239)
5 Hold each value for 5 seconds