Prerequisite: The volume of the vessel must be known.
Sensor Mode (2.1.3.)
Global Pump Totalizer Operation = Pumped volume
Material (2.1.6.) (Page 165) Global *Liquid
These parameters are as
shown above.
Response Rate (2.3.4.)
Global *Medium (1.0 m/ min)
Transducer (2.1.5.)
Global XPS-10 (singlepoint
Units (2.1.1.) (Page 162)
Empty (2.2.4.) (Page 170)
Vessel Shape (2.7.2.)
Global Flat Level Bottom Tank shape is Flat Level Bot-
Maximum Volume (2.7.3.)
Global 17.6 Max volume is 17.6 m
3
or
Relay Function (2.8.1.4.)
1 Alternate Duty Assist Sets Relays 1, 2, and 3 as a
pump group using Alternate
Duty Assist.
Relay Function (2.8.1.4.)
2 Alternate Duty Assist
Relay Function (2.8.1.4.)
3 Alternate Duty Assist
ON Setpoint (2.8.1.5.)
1 1.0 Sets the ON setpoints for the
pump group.
ON Setpoint (2.8.1.5.)
2 1.2
ON Setpoint (2.8.1.5.)
3 1.4
OFF Setpoint (2.8.1.6.)
1 0.2 Sets the OFF setpoints for the
pump group.
OFF Setpoint (2.8.1.6.)
2 0.2
OFF Setpoint (2.8.1.6.)
3 0.2
1. Press the LEFT arrow to go to Measurement View mode.
2. Once there, press the DOWN arrow
to show Measurement View 2.
3. Press the LEFT arrow
until Totalizer is shown.